ANTSPACE HK3 V6 Plate heat exchanger

Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide

Download the Bitmain ANTSPACE HK3 V6 plate heat exchanger manual for HK3 sites that reject heat through an external cold-side water loop. It covers the install profile, utility requirements, and maintenance work that differ from the tower-based manuals.

Manual revision V2.0.5
Server class 210 S19 Hydro units
PHE capacity 1200 kW
Cold-side loop 0-30C water
Plate heat exchanger manual reference image

The PHE branch matters because it changes the heat-rejection story completely. Instead of tower fans and wet hardware, the HK3 V6 plate heat exchanger manual is built around an external cold-side water source and the flow conditions needed to make that exchange work.

Teams searching HK3 plate heat exchanger guidance usually need cold-side loop requirements and exchanger-specific maintenance notes, not dry tower placement details.

PDF Download

Download the Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide PDF

Download the PDF, then use the sections below to review specs, setup steps, power and cooling requirements, maintenance notes, troubleshooting details, and revision history for Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide.

V2.0.5 May 2024 84 pages

Comparison

Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide: Version Differences

  • The PHE guide is the HK3 V6 branch that replaces tower heat rejection with water-water heat exchange through a plate heat exchanger.
  • It keeps the HK3 container at about 1.05 MW, but the external heat-rejection package shifts to a 1200 kW exchanger with cold-side water limits and flow requirements.
  • The PHE manual drops tower hoisting and spray-water sections and replaces them with PHE installation and exchanger service content.
  • Use the PHE manual when the site depends on an external water loop instead of atmospheric cooling.

Quick Specs

Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide Specs and Requirements

Container dimensions 6058 x 2438 x 2896 mm
High-computing server capacity 210 S19 Hyd. series servers
Standard / max power 1047 kW / 1050 kW
PHE heat dissipation 1200 kW
Cold-side water window 0-30C, 33-110 m3/h cold-side flow
Hot-side flow / interface 100 m3/h hot-side flow, DN100 PN16 interface

Installation

Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide Setup Highlights

  • Level the HK3 container before installation and then move directly into plate heat exchanger installation rather than tower placement.
  • Install the PHE branch, exhaust fans, and power distribution gear in the sequence the manual calls out.
  • Verify the cold-side loop is available and correctly sized before treating the container as ready for commissioning.
  • Use the onsite installation summary as the final gate because the missing cold-side loop is the fastest way to stall a PHE deployment.

Utilities

Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide Power and Cooling Requirements

  • The PHE branch keeps the HK3 container's standard 1047-1050 kW power envelope and >=85 m3/h container flow requirement.
  • Heat rejection moves into a 1200 kW plate heat exchanger instead of a tower.
  • The exchanger's cold-side water should stay between 0C and 30C, with 33-110 m3/h flow, while the hot-side flow target is 100 m3/h.
  • Facility teams should use this manual for procurement when they need cold-side loop specs instead of tower specs.

Operations

Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide Operation Notes

  • The product manual still includes system pressurization, replenishment, electrical wiring, power-on/power-off, and touch-screen operation.
  • The exchanger depends on a reliable cold-side water source instead of fan-driven atmospheric rejection.
  • Use the PHE branch whenever the site's utility or facility design already centers on secondary water loops.
  • Operators should document whether the field system is tower-based or PHE-based before making service decisions.

Maintenance

Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide Maintenance Notes

  • The PHE guide includes routine failure handling for the plate heat exchanger and a dedicated exchanger maintenance section.
  • Maintenance work involving fouling risk, cold-side water quality, or exchanger isolation belongs here instead of in the tower manuals.
  • Because the PHE branch still shares the HK3 container, container-side maintenance remains familiar even while the heat-rejection branch changes.
  • The guide also includes an 'other system maintenance' section beyond the exchanger itself.

Troubleshooting

Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide Troubleshooting Notes

  • The troubleshooting chapter separates container faults from PHE routine failures.
  • Send technicians here when the issue sits on the cold-side loop instead of a tower fan bank.
  • If the site is misidentified as a tower-based HK3 build, compare the field interface sizes and heat-rejection hardware against this manual first.

Files

Bitmain ANTSPACE HK3 V6 Plate Heat Exchanger Guide PDF Download and Revision History

Product Manual

HK3 V6 Plate Heat Exchanger Product Manual

Variant-specific PHE guide with cold-side water requirements and exchanger maintenance details.

Version
V2.0.5
Date
May 2024
Pages
84

Revision Archive

  • Plate heat exchanger product manual V2.0.5 · May 2024

    Current downloadable PHE manual with cold-side loop specs and exchanger-specific maintenance content.

Next Steps

Keep Exploring ANTSPACE and Hydro Content

Need Help Planning a Bitmain Hydro Container Deployment?

We can help you compare HK3, HW5, and HD5 platforms, sort out utilities and heat rejection, and align the right manual with the hardware you have in the field.