# Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide

> Download the Bitmain ANTSPACE HD5 V1 manual and review the dual-loop HD5 architecture, larger server capacity, dry cooling tower specs, and maintenance workflow.

Canonical: https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/bitmain-antspace-hd5-v1-dry-cooling-tower-guide/
Last updated: 2026-04-09

ANTSPACE HD5 V1 Dry cooling tower

## Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide

HD5 is the largest and most operationally different container in this library. It introduces a dual A/B liquid-cooling architecture, a 308-server density target, and a much heavier power and weight profile than HK3 or HW5.

Manual revision **V1.0.2**

Container size **12196 x 2438 x 2896 mm**

Server capacity **Up to 308 S21/S19 Hydro servers**

Standard / max power **1512 kW / 1665 kW**

The HD5 manual marks another major break in the Bitmain container line. The document describes two A/B liquid-cooling systems that can run independently or together while sharing a main control cabinet.

That architecture changes deployment, operations, and maintenance, so crews need to read the manual through planning and service work, not installation alone.

PDF Download

## Download the Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide PDF

Download the PDF, then use the sections below to review specs, setup steps, power and cooling requirements, maintenance notes, troubleshooting details, and revision history for Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide.

V1.0.2 January 2025 100 pages

[Download PDF](<https://miningstore.com/downloads/bitmain/antspace/bitmain-antspace-hd5-v1-dry-cooling-tower-product-manual.pdf>) [View Revisions](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/bitmain-antspace-hd5-v1-dry-cooling-tower-guide/#downloads-and-revisions>)

Comparison

## Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide: Version Differences

- HD5 introduces two A/B liquid-cooling thermal systems that can run separately or together while sharing a main control cabinet.

- The container grows to support up to 308 S21/S19 Hydro servers, well above the 210-unit HK3 and HW5 families.

- Power scales up sharply: 1512 kW standard, 1665 kW maximum, and 1200A x4 main switching capacity in the distribution layer.

- HD5 uses a dry-cooling-tower system with a 1500 kW tower package and DN100 external interfaces instead of HW5's dry-wet branch.

Quick Specs

## Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide Specs and Requirements

| Container dimensions | 12196 x 2438 x 2896 mm |
| --- | --- |
| High-calculation server capacity | Up to 308 S21 Hyd. and S19 Hyd. series servers |
| Standard / max power | 1512 kW / 1665 kW |
| Main switching capacity | 1200A x 4 |
| Dry cooling tower capacity | 1500 kW |
| Interfaces / flow | DN100 PN16 external interface, rated flow 67.2-73.9 m3/h depending on pump frequency |

Installation

## Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide Setup Highlights

- Level the container, install the dry-cooling towers, lift them into place, and lay out the intermediate connection pipework exactly as the HD5 guide shows.

- Treat the A and B cooling systems as a commissioning concern from day one because the manual describes them as separate loops that can run independently.

- Use the distribution-work chapter carefully because HD5 has a heavier electrical and switching profile than HK3 or HW5.

- Complete the onsite installation summary before power-up so the A/B loop architecture is fully validated.

Utilities

## Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide Power and Cooling Requirements

- HD5 uses forced-air dry cooling towers only in this manual, not dry-wet or PHE variants.

- The container supports 1512 kW standard power and 1665 kW maximum power, with 1200A x4 main switching capacity.

- The dry cooling tower package is rated at 1500 kW and \<=80 kW operating power.

- Rated flow is shown as 67.2-73.9 m3/h depending on pump frequency, which is different from the \>=85 m3/h target used in the HK3/HW5 manuals.

Operations

## Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide Operation Notes

- The manual covers system use, pressurization, rehydration, electrical wiring, power-up/power-down, and touch-screen operation from the perspective of the A/B system split.

- Operators can energize loop A, loop B, or both depending on the site's configuration and available server population.

- Field builds using dual-loop HD5 architecture should stay on this manual instead of the single-loop HK3 or HW5 guides.

- The larger server count and heavier power profile make disciplined startup sequencing even more important on HD5.

Maintenance

## Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide Maintenance Notes

- The HD5 guide includes dedicated container troubleshooting, dry cooling tower troubleshooting, and maintenance/upkeep sections.

- Because the system can run as A, B, or both, maintenance planning needs to account for loop isolation and staged service windows.

- HD5 is not the place to improvise with HK3/HW5 service habits; the guide's own architecture differences justify a separate maintenance playbook.

- Use the HD5 guide to compare expansion plans against smaller Bitmain container families.

Troubleshooting

## Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide Troubleshooting Notes

- Use the HD5 manual first when the site has an A/B loop issue, because that architecture does not exist in HK3 or HW5.

- The dry cooling tower troubleshooting section is separate from the container troubleshooting section, which helps isolate whether the problem is in the loop or the tower package.

- HD5's power scale means distribution and loop-state checks should happen before server-level assumptions are made.

Files

## Bitmain ANTSPACE HD5 V1 Dry Cooling Tower Guide PDF Download and Revision History

Product Manual

### HD5 V1 Dry Cooling Tower Product Manual

Covers the HD5 dual-loop A/B architecture and the larger 308-server container footprint.

Version

V1.0.2

Date

January 2025

Pages

100

[Download PDF](<https://miningstore.com/downloads/bitmain/antspace/bitmain-antspace-hd5-v1-dry-cooling-tower-product-manual.pdf>)

### Revision Archive

- **HD5 V1 product manual** V1.0.2 · January 2025

  Current HD5 dry cooling tower manual with dual-loop A/B architecture and the larger 308-server configuration.

Next Steps

## Keep Exploring ANTSPACE and Hydro Content

- [Browse the ANTSPACE Manual Library](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/bitmain-antspace-container-guides/>) - Move between HK3, HW5, and HD5 guide families without losing the version and cooling-method context.

- [Return to the Hydro Guide](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/>) - Use the main hydro hub to connect manuals with deployment, maintenance, troubleshooting, and buying guidance.

- [Bitmain ANTSPACE HW5 V1 Dry-Wet Tower Guide](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/bitmain-antspace-hw5-v1-dry-wet-tower-guide/>) - Download the Bitmain ANTSPACE HW5 V1 dry-wet tower manual and review the larger HW5 container specs, installation workflow, and tower requirements.

- [Bitmain ANTSPACE HK3 V7 Dry Tower Guide](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/bitmain-antspace-hk3-v7-dry-tower-guide/>) - Download the Bitmain ANTSPACE HK3 V7 dry tower manual and review the updated dry tower specs, higher container power, and added installation features.

- [Bitmain ANTSPACE HK3 V6 Dry Tower Guide](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/bitmain-antspace-hk3-v6-dry-tower-guide/>) - Download the Bitmain ANTSPACE HK3 V6 dry tower manual and review the specs, installation, operation, and maintenance details for the split dry-tower variant.

## Related
- [Browse the ANTSPACE Manual Library](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/bitmain-antspace-container-guides/>)
- [Return to the Hydro Guide](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/>)
- [Bitmain ANTSPACE HW5 V1 Dry-Wet Tower Guide](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/bitmain-antspace-hw5-v1-dry-wet-tower-guide/>)
- [Bitmain ANTSPACE HK3 V7 Dry Tower Guide](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/bitmain-antspace-hk3-v7-dry-tower-guide/>)
- [Bitmain ANTSPACE HK3 V6 Dry Tower Guide](<https://miningstore.com/mining-services/hydro-cooled-bitcoin-mining-guide/bitmain-antspace-hk3-v6-dry-tower-guide/>)